Temperature Sensor Selector
SelectorCompare sensor curve, measurement range, installation and transmitter power with your BAS input.
Open selectorEngineering tools
Read temperature from resistance, or find the expected resistance at a known temperature.
Select the exact sensor curve and conversion direction, then enter resistance or temperature with its unit. Results update as you edit. Use nominal point loads a reference example; the table interval changes only the displayed rows.
Enable JavaScript to look up values.
| Temperature (°C) | Temperature (°F) | Resistance (Ω) | Resistance (kΩ) | Lookup position |
|---|
Curve reference: Sensor curve documentation
10k Type II, Type III and 1k Pt 375 use BAPI's published nominal resistance points with linear interpolation between them. Pt1000 / 1k Pt 385 uses the Callendar–Van Dusen equation. Every result shows °C, °F, Ω and kΩ.
Lookup is limited to the included reference interval. Out-of-range readings do not produce extrapolated temperatures. Table endpoints are included; changing the displayed table interval does not change the underlying interpolation method. Values are nominal estimates, not a calibration certificate.
“1k Pt” and “Pt1000” describe the same nominal resistance at 0°C. The 375 and 385 curves differ; match the sensor and controller curve. Lead-wire resistance, sensor tolerance and self-heating are not compensated by this lookup.
Sources, supported ranges and calculation detailsFor either 10k thermistor, 10,000 Ω corresponds to 25°C / 77°F. A 1,000 Ω platinum RTD corresponds to 0°C / 32°F. Away from these nominal points, choose the correct curve before interpreting the reading.
Compare sensor curve, measurement range, installation and transmitter power with your BAS input.
Open selectorConvert both ways between analog signals and engineering values, or map 4–20mA directly to 0–10V.
Open calculatorConvert common BMS units for flow, temperature, volume, pressure, dimensions, velocity, power, energy, and torque.
Open calculator