Motor Current & Current Sensor Range

Estimate running line current from shaft horsepower, efficiency, voltage, phase, and power factor; find a matching sensor range.

Quick start

Enter motor shaft horsepower, efficiency and power factor, then choose supply phase and voltage. Select Calculate to estimate running current and compare the five listed sensor ranges. Use line-to-line voltage for balanced three-phase supply.

Inputs

Calculation inputs

Result

Enable JavaScript to calculate.

Method & assumptions

1φ: I = HP × 745.699872 / (V × η × PF)
3φ: I = HP × 745.699872 / (√3 × VLL × η × PF)

Efficiency η is the entered percentage divided by 100. HP is mechanical shaft output at the evaluated load. A rated HP input estimates operation at rated shaft output, not actual part-load current. The sensor range is the smallest of 0–10, 0–20, 0–50, 0–100, or 0–150 A containing the unrounded result.

Reference: ABB / Baldor · Power factor and efficiency · Methods, conversion conventions, and source notes

Worked example

10 HP, 90% efficiency, three-phase, 460 V, and PF 0.85 gives approximately 12.234 A; the listed range is 0–20 A.

Frequently asked questions

Is this measured full-load current?

No. It is an estimate from supplied shaft power, efficiency, and power factor. Use nameplate or measured current where available.